XCSA502EX

Safety switch XCSA, metal, 1NC+2NO, slow break, ATEX/IECEx

arrow

COMMERCIALISED

Expand all

Datasheet

Range of product
Telemecanique Safety switches XCS
Product or component type
Safety switch
Device short name
XCSA
ETIM classification
ETIM 9 - EC002592 - Position switch with separate actuator
Head type
Key operated turret head
Material
Metal
Body material
Zamak
Head material
Zamak
Number of poles
3
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1, can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1, can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to IEC 61508
Safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
Locking options description
Without locking of actuator
Product certifications
IEC-Ex INE 17.0020X
INERIS 04ATEX0014X
Marking
II2 D-Ex tb IIIC T85°C Db IP67
Directives
2014/34/EU - ATEX directive
Standards
EN/IEC 60079-0
EN/IEC 60079-31
Indivisible sale quantity
1
Actuator force for extraction
20 N
Mechanical durability
1000000 cycles
Minimum actuation speed
0.01 m/s
Cable entry number
1 tapped entry for M20 x 1.5 cable gland (included) 7-13 mm
Contact code designation
A300, AC-15 (Ue = 120 V, Ie = 6 A) conforming to EN/IEC 60947-5-1, A300, AC-15 (Ue = 240 V, Ie = 3 A) conforming to EN/IEC 60947-5-1, Q300, DC-13 (Ue = 125 V, Ie = 0.55 A) conforming to EN/IEC 60947-5-1, Q300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1
Electrical connection
Terminal
Positive opening
With NC contact
Contacts type and composition
1 NC + 2 NO
Contact operation
Slow-break, break before make
Operating rate
10 cyc/mn for maximum durability
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage
300 V conforming to UL 508, 500 V conforming to EN/IEC 60947-1, 300 V conforming to CSA C22.2 No 14
[Ithe] conventional enclosed thermal current
10 A
Electrical shock protection class
Class I conforming to EN/IEC 60536
Short-circuit protection
10 A cartridge fuse type gG (gl)
Clamping connection capacity
1 x 0.5...2 x 1.5 mm² with or without cable end
Local signalling
Without
Product weight
0.44 kg
IP degree of protection
IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…70 °C
Shock resistance
10 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance
5 gn (f= 10-500 Hz) conforming to IEC 60068-2-6
Protective treatment
TC
Dust zone
Zone 21 - 22
California proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Warranty
18 months
Country of origin
FR (France)
Unit type of package 1
PCE
Number of units in package 1
1
New Package 1 GTIN-13
3666916059241
Package 1 height
6.5 cm
Package 1 width
6.5 cm
Package 1 length
15.8 cm
Package 1 weight
0.54 kg
Unit type of package 2
S02
Number of units in package 2
12
New Package 2 GTIN 14
13666916059248
Package 2 height
15 cm
Package 2 width
30 cm
Package 2 length
40 cm
Package 2 weight
6.789 kg
Unit type of package 3
CAR
Number of units in package 3
1
New Package 3 GTIN 14
23666916059245
Package 3 height
15.8 cm
Package 3 width
6.2 cm
Package 3 length
6.5 cm
Package 3 weight
0.544 kg

Expand all

Documents & Downloads

Document name
Date
Size

Back to top