XMLDM02V1S11

Pressure switch, XMLDM, pressure range -1 bar, fixed scale, 2CO, 2 stages, for vacuum

arrow

COMMERCIALISED

Expand all

Datasheet

Range of product
Telemecanique Pressure sensors XM
Pressure sensor type
Electromechanical vacuum sensor
Product or component type
Electromechanical pressure sensor
Device short name
XMLD
Product specific application
Dual stage
ETIM classification
ETIM 9 - EC000243 - Pressure switch
Enclosure material
Zinc alloy
Materials in contact with fluid
304L stainless steel
nitrile
zinc alloy
Pressure switch type of operation
Detection of 2 single thresholds
Operating position
Any position
Pressure sensor size
-1 Bar
Maximum permissible accidental pressure
9 Bar
Maximum permissible pressure - per cycle
5 Bar
Destruction pressure
18 Bar
Pressure actuator
Diaphragm
Controlled fluid
Air (0-70 °C), fresh water (0-70 °C), hydraulic oil (0-70 °C)
Fluid connection type
G 1/4 (female) conforming to ISO 228
Local display
Without
AWG gauge
AWG 20...AWG 14
Scale type
Fixed differential
Setting
External
Product certifications
CSA
UL
Standards
CE
CSA C22.2 No 14
IEC 60947-5-1
UL 508
Indivisible sale quantity
1
Mechanical durability
3000000 cycles
Cable entry
Cable gland 9-13 mm
Repeat accuracy
2 %
Electrical connection
Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²
Electrical circuit type
Control circuit
Contacts type and composition
2 C/O snap action, silver contacts, 2 C/O staggered, silver contacts
Terminals description ISO n°1
(13-14-11-12)OF
Terminals description ISO n°2
(23-24-21-22)OF
Operating rate
120 cyc/mn
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
[Ui] rated insulation voltage
300 V conforming to UL 508, 500 V conforming to IEC 60947-1, 300 V conforming to CSA C22.2 No 14
[In] rated current
3 A, B300, AC-15 (Ue = 120 V) conforming to IEC 60947-5-1, 1.5 A, B300, AC-15 (Ue = 240 V) conforming to IEC 60947-5-1, 0.1 A, R300, DC-13 (Ue = 250 V) conforming to IEC 60947-5-1
Resistance across terminals
25 mOhm conforming to IEC 255-7 category 3, 25 mOhm conforming to NF C 93-050 method A
Electrical shock protection class
Class I conforming to IEC 1140, class I conforming to IEC 536, class I conforming to NF C 20-030
Short-circuit protection
10 A cartridge fuse, type gG (gl)
Terminal block type
8 terminals
Natural differential at low setting
0.1 bar
Natural differential at high setting
0.1 bar
Height
158 mm
Width
55 mm
Depth
90 mm
Product weight
1015 kg
IP degree of protection
IP66 conforming to IEC 60529
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…70 °C
Shock resistance
50 gn conforming to IEC 60068-2-27
Vibration resistance
4 gn conforming to IEC 60068-2-6 (f = 30-500 Hz)
Protective treatment
TC standard version
California proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Warranty
18 months
Country of origin
CZ (Czech Republic)
MA (Morocco)
Unit type of package 1
PCE
Number of units in package 1
1
New Package 1 GTIN-13
3666916026113
Package 1 height
6 cm
Package 1 width
10.5 cm
Package 1 length
14 cm
Package 1 weight
1.015 kg
Unit type of package 2
S01
Number of units in package 2
4
New Package 2 GTIN 14
13666916026110
Package 2 height
15 cm
Package 2 width
15 cm
Package 2 length
40 cm
Package 2 weight
0.229 kg
New Package 3 GTIN 14
23666916026117

Expand all

Technical Drawings

Dimensions

epds
  • (1) 1 fluid entry, tapped G1/4 (BSP female)
  • (2) 1 electrical connections entry, tapped Pg 13.5
  • Ø : 2 elongated holes Ø 10.2 x 5.2

Wiring Diagram

Terminal Model

epds
  • (a) Contact 1
  • (b) Contact 2

Operating Curves

High Setting Tripping Points of Contacts 1 and 2

epds
  • (x) PH1 setting (falling pressure)
  • (y) PH2 setting (falling pressure)
  • 1 : Maximum differential
  • 2 : Minimum differential

Operating Curves

Natural Differential of Contacts 1 and 2

epds
  • (x) PH1 setting (falling pressure)
  • (y) PH2 setting (falling pressure)
  • 1 : Maximum differential
  • 2 : Minimum differential
  • (x) Rising pressure
  • (y) Falling pressure
  • EF : Contact 1
  • GH : Contact 2

Natural Differential of Contacts 1 and 2

epds
  • (x) PH1 setting (falling pressure)
  • (y) PH2 setting (falling pressure)
  • 1 : Maximum differential
  • 2 : Minimum differential
  • (x) Rising pressure
  • (y) Falling pressure
  • EF : Contact 1
  • GH : Contact 2
  • (x) Time
  • (y) Vacuum
  • (1) Adjustable value
  • (2) Non adjustable value
  • PH : High point
  • PB : Below point

Expand all