XMLRM01G0T75

Pressure sensor, XMLR, pressure range -1 bar, output 0-10 V, G1/4A female, M12 connector, for vacuum, 24 VDC, with display

arrow

COMMERCIALISED

Expand all

Datasheet

Range of product
Telemecanique Pressure sensors XM
Pressure sensor type
Pressure transmitter
Product or component type
Electronic pressure sensors
Device short name
XMLR
ETIM classification
ETIM 9 - EC000243 - Pressure switch
Front material
Polyester
Housing material
316L stainless steel
polyacrylamide
Materials in contact with fluid
316L stainless steel
ceramic
fluorocarbon FKM (Viton)
Pressure switch type of operation
Pressure transmitter
Pressure sensor size
-14.5 PSI
Maximum permissible accidental pressure
43 PSI
Destruction pressure
43 PSI
Controlled fluid
Fresh water (0-80 °C), air (-20-80 °C), hydraulic oil (-20-80 °C), refrigeration fluid (-20-80 °C)
Fluid connection type
G 1/4 (female) conforming to DIN 3852-Y
Display type
4 digits 7 segments
Scale type
Fixed differential
Product certifications
cULus
Marking
CE
Standards
IEC 61326-2-3
UL 61010-1
Indivisible sale quantity
1
Mechanical durability
10000000 cycles
Repeat accuracy
<= 0.2 % of the measuring range
Electrical connection
Male connector M12, 4 pins
[Us] rated supply voltage
24 V DC SELV (voltage limits: 17-33 V)
[Uimp] rated impulse withstand voltage
0.5 kV DC
Current consumption
<= 50 mA
Protection type
Overload protection
overvoltage protection
reverse polarity
short-circuit protection
Type of output signal
Analogue
Analogue output function
0...10 V
Analogue output function
0...10 V
Response time on output
<= 10 ms for analog output
Linearity error
<= 0.5 % of the measuring range
Delay first up
300 ms
Operating position
Any position, but disposals can falsified the measurement in case of upside down mounting
Measurement accuracy
<= 0.6 % of the measuring range
Accuracy
<= 1 % of the measuring range
Drift of the sensitivity
+/- 0,03 % of measuring range/°C
Drift of the zero point
+/- 0,01 % of measuring range/°C
Display accuracy
<= 1 % of the measuring range
Display response time type
Fast 50 ms, normal 200 ms, slow 600 ms
Hysteresis
<= 0.2 % of the measuring range
Height
93 mm
Width
41 mm
Depth
42 mm
Product weight
0.19 kg
IP degree of protection
IP65 conforming to IEC 60529, IP67 conforming to IEC 60529
Ambient air temperature for operation
-20…80 °C
Ambient air temperature for storage
-40…80 °C
Shock resistance
50 gn conforming to IEC 60068-2-27
Vibration resistance
20 gn (f= 10-2000 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibility
Susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to IEC 61000-4-3, immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to IEC 61000-4-6, surge immunity test: 1 kV conforming to IEC 61000-4-5, electrical fast transient/burst immunity test: 2 kV conforming to IEC 61000-4-4, electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to IEC 61000-4-2
California proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Warranty
18 months
Country of origin
CH (Switzerland)
Unit type of package 1
PCE
Number of units in package 1
1
New Package 1 GTIN-13
3666916020357
Package 1 height
6.5 cm
Package 1 width
7.5 cm
Package 1 length
13 cm
Package 1 weight
0.19 kg
Unit type of package 2
S02
Number of units in package 2
20
New Package 2 GTIN 14
13666916020354
Package 2 height
15 cm
Package 2 width
30 cm
Package 2 length
40 cm
Package 2 weight
4.02 kg
Unit type of package 3
CAR
Number of units in package 3
1
New Package 3 GTIN 14
23666916020351
Package 3 height
13 cm
Package 3 width
6.5 cm
Package 3 length
7.5 cm
Package 3 weight
0.184 kg

Expand all

Technical Drawings

Dimensions

epds
  • (1) Fluid entry: G 1/4 A female

Connections and Schema

Connector Wiring

epds
  • (1) I Out or V Out
  • (2) Test Input

Analogue Output Description

epds
  • X : Pressure
  • Y : Analogue output signal
  • (1) An offset of +/-5% of nominal pressure can be compensated (with Configuration menu. : Offset Compensation)
  • (2) The Analogue curve can be adjusted from -25% to +25% of nominal pressure (with Configuration menu. : analogue end point).

Expand all

Documents & Downloads

Document name
Date
Size

2024-07-18T00:00:00.000Z

142647

2024-07-18T00:00:00.000Z

25884

2024-07-18T00:00:00.000Z

29936

2024-07-18T00:00:00.000Z

31352

2024-07-18T00:00:00.000Z

31639

2024-07-18T00:00:00.000Z

34103

2024-07-18T00:00:00.000Z

35864

2024-07-18T00:00:00.000Z

37878

2024-07-18T00:00:00.000Z

53788

2024-07-18T00:00:00.000Z

58872

2024-07-18T00:00:00.000Z

62595

2024-07-18T00:00:00.000Z

63201

2024-07-18T00:00:00.000Z

67776

2024-07-18T00:00:00.000Z

749170

2024-07-18T00:00:00.000Z

84578

Document name
Date
Size
Document name
Date
Size

Expand all

Related products & accessories

Back to top

arrow